Process Alarms
Monitor
plant-based measurements and provide
alarms or control simple feedback
loops with these reliable alarm
modules.
DPA Series - Auxiliary Powered, Dual Setpoint, Alarms
Dual Channel, Alarm Modules
The DPA series of trip modules can be configured for
just about any industrial input and provide two user
adjustable trip points for warning or control.
The alarm points are set up using potentiometers to
adjust setpoint and deadband. The deadband reduces
chatter when an alarm is triggered/reset by
adjusting the reset point away from the setpoint (hysteresis).
To generate an alarm when power is lost to the unit
simply select normally energized operation for one
or both of the output relays. You can also select
High/Low operation independently for each channel.
Inputs sources currently accepted
include temperature (thermocouple or RTD), DC/AC
currents and voltages, frequency, conductivity,
slidewire wiper position, resistance, differential
current and differential resistance. The input type
is governed by plug-in personality card (with
versions available for just about any industrial
input).
The housing clips onto both DIN and G rail. Wiring
connections are by plug-in connectors on the front
of the instrument.
|
Features:
- Two independent SPDT alarm outputs
- Flexible design caters for many input types
- High and Low alarms in any combination
- Stable and repeatable
- 5A switching capacity
- Completely isolated
- Easy to use
- DIN and G rail mounted
|
 Select to view Technical Data |
The DPA Series is cULus Listed, CE Approved
and complies with the RoHS directive for
hazardous materials reduction.
Micromann R Series
Universal, Auxiliary powered, Alarm modules
Micromann R series alarms offer two highly flexible
alarm channels for signal monitoring applications
with SPDT relay alarm outputs.
Their advantage over analog designs is that you can
easily set the setpoint and deadband in engineering
units from the front panel keypad (avoiding awkward
potentiometer adjustments).
Standard units have programmable setpoint, deadband,
high/low action, coil energization and variable
timer delays on each channel. Each model covers a
range of similar input signal and sensor types.
|
Versions Available Include:
- Analog current/voltage
- Temperature (thermocouple and RTD)
- Frequency based signals
- Conductivity
- Thermocouple units also incorporate sensor
burnout alarms
|
 Select to view Technical Data |
The XFA/R extends on the standard functions giving
you the option to set rate of change alarms,
deviation alarms and loss of signal alarms (for
elevated zero signals) on any standard analogue
current/voltage signal format. It also has two alarm
inhibit inputs for more complex applications.
In common with all Micromann series units they have
a four digit/character display, which you can scale
to read in any engineering unit. All parameters then
work off the displayed value. The user friendly
software makes setting up operating parameters very
easy: simply choose the settings you need using the
display and the tactile keypad.
The housing clips onto both DIN and G rail. Wiring
connections are by plug-in connectors on the front
of the instrument.
Features:
- Two versatile alarm channels
- Dual SPDT relay outputs
- Display in engineering units
- Independent setpoint, deadband,
high/low
action, coil energization and timer
delay
|
|
The Micromann Series is cULus
Listed, CE Approved and complies with the RoHS
directive for hazardous materials reduction.
|